For fire rated connections, is fire caulking always necessary?

The use of fire caulking is up to the discretion of the designer.
In a tight concealed connection, fire caulking may not bring any additional fire resistance. It is generally accepted that a connection with a gap between the two elements smaller than 1/16” [2 mm] may be considered a tight connection. As fire caulking was used in the full-scale fully loaded fire test, using fire caulking is very likely to help ease the approval process with local building authorities. The fire caulking used in our fire testing was the Hilti FS-ONE.